Using a panel as a raceway - Mike Holt's Forum

    https://forums.mikeholt.com/threads/using-a-panel-as-a-raceway.61825/
    For the record, one can never use a panelboard as a raceway, its just not physically possible.:grin:.....but you can use a cabinet or cut-out box:wink:

Can a panelboard be used as a raceway? - AskingLot.com

    https://askinglot.com/can-a-panelboard-be-used-as-a-raceway
    Can a panelboard be used as a raceway? Installing a raceway inside of a panelboard is acceptable in 725.136(C); however, there are additional issues for the panelboard enclosure. The wiring spaces in the enclosures can contain splices, taps or feed-through conductors as well as power monitoring equipment, as long as the installation complies with …

Can you use an electrical panel as a feed-through raceway for …

    https://www.howtolookatahouse.com/Blog/Entries/2021/2/can-you-use-an-electrical-panel-as-a-feed-through-raceway-for-wiring-that-is-not-connected-to-it.html
    Can you use an electrical panel as a feed-through raceway for wiring that is not connected to it? Saturday, February 6, 2021 Yes, wiring can pass through a panel without needing to have any electrical connections to it, according to the National Electrical Code (NEC-312.8).

CEC - Using a panel as a raceway - Electrician Talk

    https://www.electriciantalk.com/threads/using-a-panel-as-a-raceway.58710/
    Discussion Starter · #11 · Aug 27, 2013. Only show this user. On two occasions I was forced to cut back a pipe and put in a pull box so I could introduce a lighting contactor (instead of installing the contactor next to the panel). I was told that by the inspector that, "the panel was not to be used as a raceway".

Panel as a raceway - Electrician Talk

    https://www.electriciantalk.com/threads/panel-as-a-raceway.35687/
    Discussion Starter · #1 · Mar 9, 2012. Only show this user. We have a site with a two (2) 480/277 VAC panel's sandwiched in between them is a 208/120 VAC panel, they have utilized the 208/120 panel as a raceway passing conductors from one 480/277 panel to the other 480/277 panel. Any issues, there appears to be suficent space for the conductors.

Panelboard as raceway - Mike Holt's Forum

    https://forums.mikeholt.com/threads/panelboard-as-raceway.123034/
    A gutter (in electrical equipment parlance) is an enclosure, or sub-enclosure used to supplement wiring spaces at meter centers, distribution centers, switchgear, switchboards, and similar points of wiring systems. The enclosure has hinged or removable covers for housing and protecting electrical wires, cable, and busbars.

Using a panelboard as a raceway?? - Electric power

    https://www.eng-tips.com/viewthread.cfm?qid=211490
    short to reach a new lighting panel installation (in the. panel), but your position is pushing the envelope. RE: Using a panelboard as a raceway?? hdp (Electrical) 6 Mar 08 17:18. I believe NEC Article 312.8 allows this as long as the cross sectional area fill limitations specified are not violated.

Using a Panel or Disconnect as a Raceway : electricians

    https://www.reddit.com/r/electricians/comments/6fmx3s/using_a_panel_or_disconnect_as_a_raceway/
    312.8 says you can if you follow the rules. 300.3 says that mixing voltages is legal too, as long as the lower voltage conductors have equal or higher insulation rating as the higher rated voltages in the raceway or enclosure. Hope that is enough to get …

Panel enclosure as raceway - ECN Electrical Forums

    https://www.electrical-contractor.net/forums/ubbthreads.php/topics/170261/Panel_enclosure_as_raceway.html
    Past experience tells me that one must remove said circuits entirely from panel enclosure as it is not permissible to use a panel or disconnect enclosure as a raceway for other systems. I got to looking at 300.3 4C and 312.8 and it would seem to cover panel board enclosures so long as sufficient space exists for wire fill.

Code Quandaries - EC&M

    https://www.ecmweb.com/content/article/20893048/code-quandaries
    A. Yes, cabinets, cutout boxes, and meter socket enclosures can be used as a raceway for conductors that feed through if the conductors do not fill the wiring space at any cross section to more than 40% [312.8], as shown in the Figure. Service conductors and other conductors are permitted to be installed in the same enclosure [230.7].