Raceway grounding conductor - Mike Holt's Forum

    https://forums.mikeholt.com/threads/raceway-grounding-conductor.2552454/
    Obviously plastic conduits such as pvc would need a grounding conductor and some flexible metal conduits may need one depending on the length and ampacity of the conductors. If you are asking about emt or rigid (rmc) then no it is not required but often spec'ed by engineers Carultch and timtom58 A Ainsley Whyte Senior Member Location Jamaica

Grounding Requirements for Conductor Enclosures & Raceways

    https://www.ecmweb.com/code-quiz-of-day/article/20899678/grounding-requirements-for-conductor-enclosures-raceways
    The correct answer is: b) False Part IV of Art. 250 covers the bonding and grounding requirements for enclosures, raceways, and service cable connections. As noted in Sec. 250.86, "Except as permitted by 250.112 (I), metal enclosures and raceways for other than service conductors shall be connected to the equipment grounding conductor."

250.64(E) Raceways and Enclosures for Grounding …

    https://www.electricallicenserenewal.com/Electrical-Continuing-Education-Courses/NEC-Content.php?sectionID=866.0
    The general rule for ferrous metal raceways and enclosures containing a grounding electrode conductor requires them to be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode and to be securely fastened to the ground clamp or fitting. In the 2020 NEC, cable armor must now comply with this section.

Understanding Raceways - EC&M

    https://www.ecmweb.com/national-electrical-code/code-basics/article/20903368/understanding-raceways
    • Install as a complete system. • Securely fasten and support. • Metallic raceway can serve as an equipment grounding conductor (EGC), provided it meets the requirements of Sec. 250.118, but nonmetallic raceway must include a separate EGC (wire type) [Sec. 362.60] when an EGC is required.

Does every raceway require grounding conductor per nec? - Answers

    https://www.answers.com/Q/Does_every_raceway_require_grounding_conductor_per_nec
    Answers is the place to go to get the answers you need and to ask the questions you want. ... Does every raceway require grounding …

How to bond both ends of raceway containing grounding …

    https://diy.stackexchange.com/questions/211443/how-to-bond-both-ends-of-raceway-containing-grounding-electrode-conductors
    Ferrous metal raceways and enclosures shall be bonded at each end of the raceway or enclosure to the grounding electrode or grounding electrode conductor to create an electrically parallel path. Nonferrous metal raceways and enclosures shall not be required to be electrically continuous. (2) Methods.