    Currently, most of the manufacturers of seismic bracing hardware have a fitting to attach to CPVC piping which will provide lateral bracing. An isometric example of such lateral bracing is provided. (See Figure 1 at top of this article.)

Seismic Restraint/Bracing for 1-1/2" CPVC Main?

    https://www.meyerfire.com/daily/seismic-restraintbracing-for-1-12-cpvc-main
    There is 1-1/2" CPVC pipe running down the corridor with 1" branches going into each suite. I'm using NFPA-13 (2013). Does the 1-1/2" pipe in the corridor count as a cross-main, and thus require seismic restraint, or can it be omitted given its small size? If it does require restraint, would a Tolco 3000 clamp, 909 brace fitting, and 1" shed 10 ...

Longitudinal Seismic Bracing Options for CPVC?

    https://www.meyerfire.com/daily/longitudinal-seismic-bracing-for-cpvc
    For longitudinal bracing for CPVC and to keep the locations of the seismic requirement according to plan we typically use a tee and cap. You can install the brace on an arm over but it must the same size as the main. Manufactures of engineered composite joists do have seismic details on how to attach the swivel attachment (knuckle).

CPVC seismic brace - NFPA (fire) Code Issues - Eng-Tips

    https://www.eng-tips.com/viewthread.cfm?qid=485758
    But there is no longitudinal bracing for CPVC so you have to do a short arm over and put a lateral brace to act as longitudinal. If Cp is <0.5 then you can omit since you are <6" from top of pipe to point of attachment to structure. At least using those hangers you can omit branch line restraint regardless of Cp.

Underwriters Laboratories | Seismic Bracing | Sprinkler …

    https://www.eaton.com/us/en-us/company/news-insights/for-safetys-sake-blog/seismic-bracing.html
    For instance, a brace used on 4” or smaller pipe that was 1,000 pounds will now list at 680 pounds after September 2020. In this example, the product’s published catalog load of 1,000 pounds under the former standard …